Sign In | Join Free | My ecer.jp |
|
Brand Name : SEFIE
Model Number : SF30LE-32
Certification : CB,CE,ROHS
Place of Origin : WenZhou,China
MOQ : 2000-3000
Price : Negotiable
Supply Ability : 200000 pcs per month
Delivery Time : 14 days after receipt of deposit
Packaging Details : 240 pcs per carton, 12 pcs per box
Material : Plastic
Type : RCBO
Rated current : 6-32
Rated voltage : 240
Trippign curve : B,C,D
Pole : 1P+N
50/60Hz 230V 3KA SF30LE-32 RCBO Earth Leakage Circuit Breaker
SF30LE-32 leakage protective breaker is used in the single phase residence circuit of AC 50Hz/60Hz, rated voltage230V, used as electron shock protection, it can protect civil electron circuit from overload and short circuit This produce has advantages of small volume, high breaking capacity zero,and live wire are cut off at the same time ,also protecting person from electric shock when the live wire connected opposite.
Test procedure | Type | Test current | Inital State | Tripping or Non-tripping Time Limit | Expected Result | Remark |
a | B,C,D | 1.13In | cold | t≤1h | no tripping | |
b | B,C,D | 1.45In | after test a | t<1h | tripping | current in the 5s in the increase of stability |
c | B,C,D | 2.55In | cold | 1s<t<60(In≤32A) | tripping | |
d | B | 3In | cold | t≤0.1s | no tripping | turn on the auxiliary switch to close the current |
C | 5In | |||||
D | 10In | |||||
e | B | 5In | cold | t<0.1s | ture on the auxiliary switch to close the current | |
C | 10In | |||||
D | 50In | |||||
The terminology "cold state"refes to that no load is carried brfore testing at the reference setting temperature |
![]() |
D Curve 20a RCBO Circuit Breaker 1P+N Pole For Electronic Shock Protection Images |